Call: 0800 193 3200 | Email: info@ukwatermeter.co.uk

Collection: BREEAM Water Leak Detection Systems

BREEAM WATER LEAK DETECTION PANEL

Stockshed's Leak Detection Systems, SSLDS-1 & SSLDS-2, monitor the flow of water into a building with one or two pulsed water meters. If the flow rate exceeds preset parameters an alarm condition occurs with sound and optional water supply shut off via a solenoid valve.

The SSLDS water leak detection systems activate when the flow of water exceeds the preset maximum for the preset period of time. It can identify different flows and therefore leakage rates, in accordance with BREEAM Wat 3.

These parameters can be adjusted by the user to allow for different conditions.
IMPORTANT: In order that meaningful parameters are entered, a full water audit should be carried out to establish water consumption trends over a period of time.

SSLDS-1 & SSLDS-2 BREEAM WATER LEAK DETECTION SYSTEMS

Designed to detect major water leaks and help prevent flood damage caused by leaking pipes and fittings or by vandalism. The SSLDS-1 water leak detector panel is connected to a pulse water meter installed at the site boundary or main water intake point of the building to monitor the consumption of water. An audible/visual alarm output is activated when a continuous flow of water passes through the water meter at a flow rate above a preset maximum for a preset period of time.

A Normally Open free contact is provided for connection to a BMS (Building Management System) or to activate a local sounder/beacon type alarm.

A free contact is also provided to shut off the water supply via a solenoid shut off valve if required. This contact may be programmed to suit a Normally Closed or a Normally Open solenoid valve as required.

The SSLDS-2 is for installations where a pulse water meter is installed at the site boundary and at the main intake point of the building and in addition can detect a loss of water between the site boundary and the main intake point.

OPTIONAL ACCESSORIES: 24v DC Sounder Beacon, can be hardwired locally or elsewhere in the building, programmable sound and volume. Set of 4 steel wall mounting brackets, these enable the panel to be wall mounted using screws or bolts external to the panel.

NEW FEATURES:-

SOLENOID VALVE SETUP: Enables a Normally Closed or a Normally Open solenoid valve to be selected in software. Also a timed valve service function can be set to reduce the likelihood of valve sticking due to calcification etc.

EXTERNAL ALARM INPUT: This input is available for the connection of ancillary equipment such as tape leak sensing to be interfaced to the water leak detection system.

ENCLOSURE: slightly larger at 300 x 300 x 150mm with a RH hinged door. This facilitates easier wall mounting and access to the internal terminals.


Leak Alarm System Specifications:

  • Power requirements: Universal input 100-260v AC 50/60Hz 1.5A max
  • Pulse Meter Input: 24v DC 5mA maximum for reed switch type pulse meter, programmable for 1, 5, 10 or 100 litres per pulse
  • PSU Output: 24v DC @ 1.1A for powering alarm or solenoid valves
  • Alarm Output: Normally open free relay contact rated at 5A resistive load 250v AC / 30v DC
  • Valve Output: Free relay contact rated at 5A resistive load 250v AC / 30v DC, programmable as Normally Open or Normally Closed with timed service function
  • Additional outputs: two alarm contacts are available
  • External HF/LF input: overrides internal clock
  • External alarm input: enable ancillary equipment such as tape sensing to be interfaced to the SSLDS panels
  • LCD display: 2x 16 ASCII character with LED backlight
  • Keypad: with tactile feedback 0-9 numeric keys plus navigation keys for parameter setting and monitoring
  • Parameters: Litres input range 1 – 32,767, time input range 1 minute – 45 hours, number of High Alerts to alarm: 1-99
  • Real Time clock: displaying day and time (24Hr format) with automatic GMT/BST changeover. Battery backed (10 year life).
  • Connections: via DIN rail terminals, maximum conductor size 4mm², cable entry via stuffing glands in gland plate
  • Enclosure: IP65, steel wall mounting overall dimensions 300 x 300 x 150mm (W x H x D) RAL7035 powder coated
  • Overall weight of leak alarm system: Approximately 6Kg

Please contact Stockshed for your leak detection enquiry.